Boondocks Tempe
Permit ID: FD-81157
Permit Type: E & D
1024 E Broadway Rd Tempe 85282
NA means not available. See detailed inspection reports for additional information.
Plumbing inspection conducted with superintendent by appointment. Inspection rights were delivered via email. The project is approximately 70% complete. Please ensure the following items are addressed by the completion of the project: 1) Provide ASSE 1013 reduced pressure zone backflow preventers upstream of the misting system and the glass rinsers at the bar, if installed. Certify and provide test reports. 2) Ensure that the chemical dispensing unit installed at the mop sink is installed to a dedicated water supply line. Installation on the mop sink faucet is not approved. 3) Provide air curtains over the bi-fold windows or permanently seal the windows shut. 4) Provide a clear epoxy seal to the exposed block walls in the restrooms. Ensure all large holes and gaps are effectively filled. The other option would be to installed plexi-glass or similar material on the block wall to provide a smooth, durable, non-absorbent, and easily cleanable surface. 5) Caulk-in the countertop gap throughout the bar with silicone. 6) Provide metal cove base (3/8th inch minimum) to the floor/wall junctures of the ventilation hood. 7) Provide splash guards on both sides of the bar handwash sinks, as needed. Please contact the Department to schedule the final construction inspection (100% completion with Certificate of Occupancy) at 602.506.6824. MCESD inspection report was delivered via email. No County legal action will result from this inspection.