Hundred Mile Brewing Company, LLC
Permit ID: FD-86011
Permit Type: E & D
690 N Scottsdale Rd Tempe 85281
NA means not available. See detailed inspection reports for additional information.
Construction inspection for a Class 4 10+ E&D permit was conducted with superintendent Todd K. by appointment. Inspection rights were delivered via email. The project is approximately 50% complete. Please ensure the following items are addressed by the completion of the project: 1) The facility will be following outdoor bar requirements due to the presence of garage roll-up doors. The facility will need to provide tight-fitting, self-closing doors to all kitchen entrances to seal the kitchen. The soda fountain system at the service station is not approved. Please provide soda gun systems only. 2) Install ASSE 1013 reduced pressure backflow preventers upstream of the soda carbonator, glycol system, keg washers, and glass rinsers at the bars. Ensure no copper is located downstream of the soda carbonator backflow. Certify and provide test reports. 3) Install ASSE 1022 dual check backflow preventers upstream of all non-carbonated beverage equipment. 4) All hose bibs must be equipped with ASSE 1011 backflow preventers. 5) The air curtain above the back exterior door must be micro-switch activated and all manual switches must be disabled or removed. 6) Provide metal cove base (3/8th inch minimum) to the walk-in cooler exterior floor/wall junctures and at the vent hood. Please contact the Department to schedule the equipment inspection (50-75% completion) at 602.506.6824. MCESD inspection report was delivered via email. No County legal action will result from this inspection.