Angie's Lobster
Permit ID: FD-86521
Permit Type: E & D
835 W Baseline Rd Space Tempe 85283
NA means not available. See detailed inspection reports for additional information.
Equipment inspection for a Class 3 0-9 E&D permit was conducted with superintendent Chad P. by appointment. The project is approximately 90% complete. Please ensure the following items are addressed by the completion of the project: 1) Install an ASSE 1013 reduced pressure backflow preventer upstream of the soda carbonator. Ensure no copper or copper alloys are downstream of the backflow. Certify and provide a test report. 2) Provide a separate dedicated water line for the mop sink chemical dispenser unit. 3) Provide 12"x12"x12" dry wells for the walk-in cooler condensate, as discussed. Ensure the well is filled with river rocks. 4) Ensure all air curtains are activated soley by the micro-switches. No manual switches are approved. 5) Provide hose bib vacuum breakers to the hose bib faucets located at the exterior of the building. 6) Ensure all sink fixtures are caulked to the walls with silicone. 7) Caulk all escutcheon plates and plumbing penetrations throughout the facility with silicone. At the final construction inspection, ensure hot water measuring 120' F minimum is provided to the plumbing system and all refrigerators are on and measuring at 41' F or below. MCESD inspection report was delivered via email. No County legal action will result from this inspection.